19 Test Call
If the system is fitted with a DC6, it is possible for
the control panel to make the DC6 send a
timed test call to the central station. The “Test
Call” timer sets the period of activation, i.e.,
000=Disabled, 001=daily, 007=weekly etc.
Once programmed the digicom will send the
test call at the hour defined by timer 23. This
timer has a working range of 000-199 days.
(Default: 000 Days)
20 Alarm Confirmation
This timer controls the duration of the “Alarm
Confirmation” period. The timer has a working
range of 000-199 minutes. (Default: 30 mins)
21 Line Flt Dly
This timer delays the “audible” line fault
indication when a telephone line fault occurs.
The display and any outputs programmed as
“Line Fault” are not affected. If the timer is set to
199 the monitoring of line fault is disabled. This
timer has a working range of 000-199 minutes.
(Default: 000 Mins)
22 Service Time
The installation company may use this timer to
periodically generate a “SERVICE REQUIRED”
message so that the user is reminded that a
service call is required. The users may continue
to set and unset the system. When the
engineer attends the site and enters their
passcode the message is cleared. The service
timer is re-started when the engineer re-selects
this timer option. To disable this feature set the
timer to 000. This timer has a working range of
000-199 months. (Default: 000 Months)
23 Test Call At
This timer is used in conjunction with timer 19, it
controls the hour at which a test call is sent to
central station. For example, if the timer is set to
014 the test call will be signalled at 14.00
(2.00pm). This timer has a working range of 000
- 023. (Default: 003)
Setting Modes [1.6]
The setting mode for full set and each part set can
be configured to the following setting modes:
1 Final Exit
The system will set when the “Final Exit” circuit is
activated and after the “Settle Time” has
expired.
2 Exit Terminator
The system will set when the “Final Exit” circuit is
activated, the “Exit Terminator” button is
pressed and after the “Settle Time” has expired.
3 Timed Exit
The system will set when the “Exit Time” has
expired or if the “Exit terminator” button is
pressed and the “Settle Time” has expired.
4 Instant
The system will set instantly.
5 Deferred
As timed exit, however, if any circuits are
activated during the exit procedure the exit
timer is restarted.
6 Lock Set
To use this method you must install a lock
switch with the contacts connected to a
lockset zone type.
33
TS690 & TS690ID Installation Manual Engineer’s Menu 1
System Timers
Enter Number >--
System Timers
Exit Time... 030
System Timers
Exit Time... 045
Enter new timer value
Timer Type
Timer value
5
ENT
Enter timer No.
e.g. 04 for exit time
ENT
e.g. 045
Engineers menu 1
Select Options :-
StarburstLCD
LED
E1 -
ENGR 1 -
Ti..--
TIMER --
030
030
045
045
System Timers Flowchart