System Timers [1.5]
The system timers are as follows:
00 Abort Delay
This timer sets the period in which the alarm
signal may be aborted following an alarm
condition. When an alarm occurs, the “Abort
Output” (043) is only activated if the system is
unset within this period. If the system is unset
after this period the abort output is NOT
activated. The “Alarm” (005) output is also
restored when the abort output is activated.
This timer has a working range of 000-199
seconds. (Default: 180 Secs)
01 No. Re-arms
At the end of the bell duration time the system
re-arms all circuits that are healthy. Circuits that
are still in an alarm condition are isolated until
they change to a healthy condition. This
counter controls the number of times that a
"circuit" will re-arm before it is locked out of the
system. This counter has a working range of
000-199. (Default: 003)
02 Settle Time
When setting the system by “Final Exit” or “Exit
Terminator”, detectors that are on the exit route
sometimes take 3-4 seconds to settle after
activation. The delay programmed in this timer
is used to allow these detectors to settle before
the system or area is set. This timer has a
working range of 000-199 seconds. (Default:
007 Secs)
03 Pset Com. Dly
When the system is part-set the
communication of an alarm signal to the
central station can be delayed by the value
set in this timer. If the timer is set to 199 the
part-set communications are disabled. This
timer has a working range of 000-199 seconds.
If you set this timer to 199 then the control
panel overrides keypad lockout during
part-set.
Cooper Security also recommends that
you change the digicom output type
(see Eng 1.2 or 1.3) from 008 to 047. This
will stop the control panel transmitting a
close signal when the users part set the
system.
(Default: 000 Secs)
04 Exit Time
This timer sets the delay between the user
initiating the exit procedure and the system (or
area) actually setting. If during the exit time an
“Exit Terminator” circuit is activated the exit time
is cancelled and the system sets immediately.
This timer has a working range of 000-199
seconds. (Default: 030 Secs)
05 Entry Time
When the system is set or part-set, and the entry
procedure is initiated, the entry timer starts to
count down. If a valid user passcode has not
been entered when the timer reaches zero,
the internal sounders are activated and the
“2nd Entry” timer is started. This timer has a
working range of 000-199 seconds. (Default:
015 Secs)
31
TS690 & TS690ID Installation Manual Engineer’s Menu 1
Program circuits
Enter CCT No.>--
CCT 04 NIGHT
CCT 04 F.EXIT
>********
CCT 04 F.EXIT
>*******C
Enter circuit type:
= Not Used
=Night
= 24hr
= PA Silent
Circuit No.
Attributes
Circuit Type
4
0
1
2
3
ENT
Enter circuit No.
e.g. 04
=Fire
= Auxiliary
= Final Exit
5
6
7
ENT
e.g. 7 for Final Exit
Select attributes:
= ccessA
= KnockD
=estT
1
2
3
=esetR
=onitoredM
=ntryE
5
6
7
ENT
e.g. 8 for chime
= PA Audible
4
=mitO4 =himeC8
Engineers menu 1
Select Options :-
StarburstLCD
LED
E1 -
ENGR 1 -
CT.--
CCT NO.--
NITE
NIGHT
04
FE
04
F.EXIT
04
FE
CHI
04
F.EXIT
CHIME
= Exit Terminator
=KeyPoint
8
9
Program Circuits Flowchart