
and the circuit remains active until the end of
the confirmation time then the control panel
omits the active zone and triggers the Active
Omit output. The control panel deactivates
the output when a user disarms the system.
Use existing output type 036 = System Open to
indicate Unset Complete.
100 - 137 Circuit Mimic
Will mimic (active when circuit is active) circuits
01 to 38 respectively.
200 - 237 Circuit Alarms
Active when a circuit causes an alarm, or is
activated during a walk test, for circuits 01 to
38 respectively.
Following a wallk test, the operator can
confirm the operation of all the appropriate
circuits at a mimic panel. The control unit
clears these indications when the operator
enters a valid passcode.
Program Circuits [1.4]
The TS690 can monitor up to 14 detection circuits,
whereas the TS690ID can monitor up to 38
detection circuits. Each circuit must be
programmed in order for the system to respond
correctly.
Circuit Types
The circuit type defines how the circuit will respond
when it is triggered. The following circuit types are
available:
0 Not Used
A circuit that will never generate any alarm.
1 Night
A circuit that will generate a full alarm when the
system is set.
2 24hr
A circuit which is monitored at all times. When
triggered in the unset condition a local alarm is
generated and when triggered in the set
condition a full alarm is generated.
3 PA Silent
A circuit which is monitored at all times. When
triggered it will activate any outputs that are
programmed as P.A.
4 PA Audible
A circuit which is monitored at all times. When
triggered it will activate any outputs that are
programmed as P.A. and generate a full
alarm condition.
5 Fire
A circuit that is normally connected to a smoke
detector. When triggered it will generate a fire
tone on the internal sounders, the external
sounders are pulsed for the bell duration and
any outputs programmed as fire will be
activated.
6 Auxiliary
A circuit which is monitored at all times. When
triggered it will activate any outputs
programmed as Auxiliary.
7 Final Exit
This must be the first detector or door contact
that is triggered when entering the protected
area. When the setting mode for the system is
programmed for Final Exit setting, opening
and closing of this circuit during the exit
procedure will cause the system to set. Once
set, activation of this circuit will start the entry
timer.
8 Exit Terminator
A circuit that is normally connected to a push
button outside the protected premises, which
can be used to finally set the system or area.
9 Keyswitch
(Also includes Lockset.) A circuit that may be
connected to a keyswitch to allow setting
and/or part-setting of the system.
The Keyswitch circuit has two groups of
attributes. The first group of attributes control
the wards that are set/unset when the circuit is
switched between “Healthy” and “Active”. The
second group of attributes selects the type of
Keyswitch (Momentary or Latched) or selects
the Lockswitch zone type.
When programming the Keyswitch circuit the
eight standard attributes are not available,
instead the attributes are used to select the
Keyswitch operation as follows:
[1] Full Set Group - “Healthy” to “Active”.
[2] Code Set Group A - “Healthy” to “Active”.
[3] Code Set Group B - “Healthy” to “Active”.
[4] Code Set Group C - “Healthy” to “Active”.
[5] Lockset - See Lockset Exit Mode.
[6] Momentary - Use for Momentary type
keyswitches. De-select for Latched
keyswitches.
29
TS690 & TS690ID Installation Manual Engineer’s Menu 1
Comentarios a estos manuales