DF6000 - USER MANUAL
7
System Design Guidelines
Guidelines
Systems should to the relevant local standards and codes of practice, for the UK this is BS5839 Pt 1.
DF6000 meets all the relevant requirements of BS5839 Pt 1: 2002. Installation planning is simplified by
the fact that every addressable DF6000 device contains an integral short circuit isolator. Care must be
taken to ensure that local standards requirements regarding aspects such as loop coverage, area
covered by a single spur and cable specification are observed.
There may be certain applications in which deviations from the code may be necessary and these must
be listed on the commissioning certificate. (See commissioning section).
Loop Lengths
The maximum permitted loop length is 2 km measured from the near to the far terminals on the DF6000
motherboard PCB. There is no minimum limit to loop length. Any wiring spurs off the loop must be
included within the 2 km limit. On long loop runs, the lengths of wiring rises and falls (between floors,
down to manual callpoints) must be included. Remember to include these especially when taking loop
lengths from plan drawings.
Loop Loading - Total Number of Addresses
The total number of addresses per loop is 200. this includes detectors, callpoints and all other
addressable items (e.g. MPU, MIO, loop repeaters etc.) When designing systems its recommended that
allowances are made for future expansion, Short circuit isolators are incorporated into every DF6000 loop
device, including Smoke detectors, heat detectors, sounders, callpoints and interfaces. Therefore, no
further fault protection is required, in the event of a single fault, none of the devices connected to the loop
will fail to operate as the fault will be isolated by the two adjacent devices. Spur connected devices
downstream of a cable fault will cease to function.
DF6000/PR Repeater Panels
Each repeater unit requires one address and consumes no more current from the loop than a smoke
detector. The repeater also requires a local mains supply and incorporates battery backup.
Loop Loading System Verification
Unless a loop loading calculation has already been carried out, please contact our technical support
department (01302 303350), before starting installation to verify that a proposed loop loading
arrangement is acceptable.
Section 1 - System Installation and Design