DF6000 - USER MANUAL
42
Commissioning Mode
Walk test mode allows a single engineer to test the various detectors and callpoints on a system without
always having to return to the panel either to reset the system or silence the alarms. When in
COMMISSIONING MODE, the system operates as normal except that when a detector or callpoint goes
into alarm, the alarms only operate for a few seconds and then will silence. The panel then tries to reset
the device automatically and, if successful, the alarms are operated again for a few seconds and the
installation engineer can move on to the next detector. After a full test has been carried out the engineer
can check the order in which the detectors/callpoints were operated using the DISPLAY LOG mode. This
information can also be printed on the optional printer.
When the panel is in “Walk Test Mode” the control panel inserts a different code into the log and also onto
the print-out. This is to distinguish between when a device has been tested in “Walk Test Mode” and
when a device has been triggered while in normal operation.
The following differences will occur:
1. When in the LOG mode, "One man walk test”" will appear on the display followed by the address text
and device type.
2. On the printout a “One man walk test” message will appear will appear followed by the address text
and device type.
3. During a real fire “FIRE !” Will appear on the display followed by the address text and device type.
Section 3 - Commissioning