DF6000 - USER MANUAL
29
Cable and Wiring
Only the cable types listed below are allowable for loop connections.
1. Enhanced Fire TUF
2. Fire TUF™
3. FP200
4. MICC
When choosing your preferred cable type, you must take note of the following cable and wiring
requirements.
1. The cable must be 2 core screened with an over sheath.
2. Maximum loop length with any of the above cables is 2 km
3. Maximum volt drop must be limited to 7 V.
4. The conductors should be 1.5mm minimum an no larger than 2.5mm
5. Multicore cable should not be used for detector wiring.
6. Different loops should NEVER be run within the same cable.
7. Loop feeds and returns should never be used within the same cable.
Cable Resistance
Cable Anchorage
The mains cable must be fixed securely with a 20mm cable gland. Remove a suitably located knockout
feed the cable through the gland and bolt the gland to the DF6000 backbox as shown. Secure the cable
to the side of the box using the cable clip provided.
NOTE: The mains cable tail ends must be insulated to prevent dangerous conditions arising in the event
of accidental switching on of the mains supply.
Section 1 - System Installation and Design
Core Diameter Typica l FP200 Resistance
1.0mm² 18.1 Ohms/km/Core
1.5mm² 12.1 Ohms/km/Core
2.5mm² 7.41 Ohms/km/Core
4.0mm² 4.61 Ohms/km/Core