DF6000 - USER MANUAL
45
Protocol Format
Normal Communications to Devices:
With the command bits set for the 'Normal' command and the MSB of the 3 mode bits set at 0, this
shortened version of the normal communications to each device allows the analogue reply or status from
each device to be read. This format of communication is generally used throughout all background
supervision of the addressable loop.
Alarm Interrogate Command:
This command is seen by all devices on the loop, so no address byte is required, and is periodically sent
out during normal communications. This command allows any device experiencing an alarm condition to
respond, with callpoints given the highest priority, reporting their address. This causes the control panel
to break off from general background supervision of the loop and focus directly on the device in question.
Full Protocol Format:
With the command bits set for the 'Normal' command and the MSB of the 3 mode bits set at 1, the long
version of the normal communications can be sent to any device. This would normally be done by the
panel following a response to the alarm Interrogate command, allowing the panel to check the device
address, ID and confirm that the analogue reply, or status, is truly an alarm condition before actioning the
panel sounder outputs, for example.
Viewing the Voltage and Current waveforms at the panel:
Loop 1: Using a digital storage oscilloscope, connect one channel to R34 on the loop driver card;
probe 0V clip to the 'in-board' side of the resistor. This will display the loop current. Connect the
other channel to Loop 1, S+ terminal on the main mother board. DO NOT connect the 0v clip of
this probe.
Loop 2: Using a digital storage oscilloscope, connect one channel to R36 on the loop driver card;
probe 0V clip to the 'in-board' side of the resistor. This will display the loop current. Connect the
other channel to Loop 2, S+ terminal on the main mother board. DO NOT connect the 0v clip of
this probe
Section 3 - Commissioning
Byte 1
Byte 2
Byte 3
Parity
Command
2ms
300us
300us
Start
Panel to Device Device to Panel
Response
8bits
ID
5bits
Flags
3bits
A
Loop Current
24v
typ
7.5v
0v
Mode
1.1 ms
Each Packet of Comms above must be separated by a gap of 20ms minimum where the line is held at 24v