Cooper Menvier 100 Información técnica Pagina 8

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 48
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 7
8
Standard Connections
Dimensions
1
2
3
4
5
D2
W
H
D1
H (mm) W (mm) D (mm)
395 332 115
Code Description
ULDF6000PR Passive Repeater Panel
Product Codes
Code ULDF6000PR
Description Passive Repeater Panel
Standards UL864 9
th
edition
System Indicators
LED’s Power on, Alarm, Trouble, Test, Supervisory,
Scroll LED’s
Mains Input, Supervised
Voltage 120 V ac to 240 V ac, 60 Hz
Current 35 mA
SLC Field Wiring
Current 0.354 mA
Wiring Gauge 12 (max) AWG
Wiring Class Class A Style 7
Ground Fault 0.1 ohm
Supervisory, Power Limited Yes
Line Impedance 50 Ω (max)
Batteries
Batteries 1x12 V dc, 3.2 Ah, 0.1 derating
Battery Charge Current 0.4 A
Standby Period 24 hours + 30min alarm
Download Comms RS232 port
Environmental
Operating Temperature 0°C to 49°C
Humidity (Non Condensing) 0 to 93 %RH
Physical
Dimensions (H x W x D) 270mm x 332mm x 90mm
Weight 3.6kg (with batteries)
Ingress Protection IP30
Construction PC/ABS, UL94 5VA rating
Colour Light Grey or Graphite
Cable Entry 12 x 20mm knockouts top of backbox
Compatibility
Suitable for use with Menvier UL fire systems
Technical Specification
ULDF6000PR - Passive Repeater Panel
Vista de pagina 7
1 2 3 4 5 6 7 8 9 10 11 12 13 ... 47 48

Comentarios a estos manuales

Sin comentarios