ULDF6000 & ULDF6000RM Control Panels
6
Code Description
ULDF60002G 2 Loop Panel
ULDF60004G 4 Loop Panel
ULDF60002GP 2 Loop Panel c/w Integral Printer
ULDF60004GP 4 Loop Panel c/w Integral Printer
ULDF60002GNC 2 Loop Panel c/w Network Card
ULDF60004GNC 4 Loop Panel c/w Network Card
ULDF60002GPNC 2 Loop Panel c/w Integral Printer, Network Card
ULDF60004GPNC 4 Loop Panel c/w Integral Printer, Network Card
ULDF60002RM 2 Loop Panel Red Metal Box
ULDF60004RM 4 Loop Panel Red Metal Box
ULDF60002PRM 2 Loop Panel c/w Integral Printer Red Metal Box
ULDF60004PRM 4 Loop Panel c/w Integral Printer Red Metal Box
ULDF60002NCRM 2 Loop Panel c/w Network Card Red Metal Box
ULDF60004NCRM 4 Loop Panel c/w Network Card Red Metal Box
ULDF60002PNCRM 2 Loop Panel c/w Integral Printer, Network Card Red Metal Box
ULDF60004PNCRM 4 Loop Panel c/w Integral Printer, Network Card Red Metal Box
ULDFR6000L2 Rack mounted 2 Loop Panel
ULDFR6000L4 Rack Mounted 4 Loop Panel
ULDFR6000L2NC Rack Mounted 2 Loop Panel c/w Network Card
ULDFR6000L4NC Rack Mounted 4 Loop Panel c/w Network Card
Product Codes
Dimensions (Metal)
D2
W
H
D1
H (mm) W (mm) D1 (mm) D2 (mm)
398 505 48 118
H (mm) W (mm) D1 (mm) D2 (mm)
397 497 75 130
Technical Specification
Code ULDF6000 and ULDF6000RM
Discription UL Analgue Control Panel
Standards UL864 9
th
edition
Primary Operating Supply 120/240 V, 60 Hz, 2.0 A Supervised
Secondary Operating Supply
Battery Voltage 24 V dc
Battery Charge Current 1.0 A (max)
Battery Derating Factor 0.1
Battery Capacity Supervised 12 Ah (max)
Notification Appliance Circuits
Class B, Style Y, Sounder Group 1 sounder 1, Sounder Group 1 sounder 2,
Sounder Group 2 sounder 1, Sounder Group 2 sounder 2
Output Voltage 24 V dc
Output Current 0.75 (max)
Line Impedance 50 ohms
When the product is powered by 240 V ac, the
maximum current of 3.0 A is shared between
these circuits.
When the product is powered by 120 V ac, the
maximum current of 2.25 A is shared between
these circuits.
Supervised, Power limited, Regulated
Notification Appliance Circuits
Class B, Style Y, SYNC MODULE. NAC1, NAC2
Output Voltage 24 V dc
Output Current 0.5 A (max)
Line Impedance 50 ohms (max)
The maximum current of 0.5 A is shared
between these circuits.
Supervised, Power limited, Regulated
Alarm, Trouble Contacts. Relay Expansion
Unity Power Factor 30 V dc
For connection to power limited sources only
Aux Relay (AC Trouble) Contacts
Unity Power Factor 30 V dc, 1 A
For connection to power limited sources only
Signaling Line Circuit Style [7] Class [A] – (Addressable Loop)
Rated Voltage 24 V dc
Maximum Current 500 mA
Line Impedance 50 Ω (max)
Supervised, Power limited
Network SLC
Voltage 5 V dc
Current 100 mA (max)
Line Impedance 50Ω (max)
Power Limited
Limited to same-enclosure Installations
Compatibility
Suitable for use with Menvier UL fire systems
Dimensions (Plastic)
D2
W
H
D1