Code Description
UMPS-100 Pull Station, SPST Single Action, Terminals, Key Reset
+ULMCIM-C
UMPS-400X Pull Station, Explosion Proof, Single Action, Key Reset
+ULMCIM-C
UMPS-100WP Pull Station, SPST Single Action, Terminals, Key Reset
+ULMCIM-C
UMPS-200 Pull Station, SPST Double Action, Terminals, Key Reset
+ULMCIM-C
Product Codes
Installation
The Series MPS Pull Station may be surface mounted
indoors with a separately ordered backbox option or
flush mounted on a standard single gang switch
plate. In either case be sure to follow local codes and
regulations. To comply with ADA standards the Pull
Station must be less than 48 inches above the floor
for front wheelchair access, and less than 54 inches
above the floor for side wheelchair access. MPS Pull
Stations, when mounted to the Series MPS-WP
Backbox with Gasket Assembly, are listed for outdoor
use and are NEMA-3R listed.
Surface Mount
A surface mount installation uses a red diecast
(MPS-WB) or sheet metal (MPS-ISB) Backbox. The
backbox has four pre-drilled mounting holes of
0.187-inch diameter. A screw size of 8 or smaller can
be used to attach the backbox to a wall. After the
backbox is in place, attach the conduit. The diecast
backbox (MPS-WB) has an opening that is tapped for
a 1/2 inch NPT fitting which may be oriented at the
top or bottom when the box is attached to the wall.
The sheet metal backbox (MPS-ISB) has conduit
knockouts. Field wiring is connected to a terminal
block as shown in the wiring drawings. The wiring
should not be wrapped around the terminal, but
placed under the clamping plate. The housing is
locked using a keylock. Unlock the housing by
turning the key clockwise and swing down the front
of the housing to make the sheet metal mounting
plate accessible. Mount the metal plate to the
backbox using the four 1/4 inch length, 8-32 screws
that are supplied. If a Breakrod (MPS-RODS) is being
used, move the PULL handle to about a 45-degree
angle with the face of the housing. Insert a breakrod
into the cavity beneath the PULL handle. Place the
PULL handle back into the normal position (flush with
the housing). While holding the PULL handle in place,
move the housing back to the upright position and
lock. The Pull Station in now ready for operation.
Flush Mount
Most flush mount installations may be attached to a
standard single gang switch box (not supplied) The
only difference between a surface mount installation
and flush mount installation is that the two 6-32
screws are placed through the slots that are centered
on the metal plate.
Standard Connection
Loop In
Loop Out
Addressable
Loop
Power
Limited
Internal
Wiring
Addressable Pull Stations