UL Product Range
33
ULCSUM355 Shop Monitor Unit
Overview
An extensive range of interfaces are available to
support the Menvier range of UL control panels,
providing solutions for most design requirements.
The ULCSUM355 shop monitor unit is designed to
enable small units with conventional fire detection to
be fully integrated with a main analogue addressable
fire system. It is ideal for applications such as
connecting individual shop units into a main
shopping centre system.
An external power supply is required to drive the 2
conventional sounder circuits. This power supply
must be UL1481 listed, regulated for fire and current
limited.
Features
• Quick and simple to install
• Accepts a zone of UL approved
conventional detectors and
callpoints
• Provides 2 conventional
sounder circuits
• Only takes a single address
• Includes output changeover
relay
• Inputs monitored for open,
short circuits and ground
trouble
Benefits
• Plug and play no hard
addressing required
• Easy to expand a system using
existing wiring
• No external short circuit isolator
required
• Reduced installation cost by
using the 2 sounder circuits